首页 >> 最新文章

等值盐密现场测量方法的研究六角螺栓

文章来源:立方五金网  |  2021-02-01

等值盐密现场测量方法的研究

中图分类号:TM835.4 文献标识码:A

文章编号:2258-8223 24-2242-25STUDY ON THE METHOD OF ESDD ON-SITE MEASUREMENTJIANG Xiu-chen, AN Ling, HAN Zhen-dong

ABSTRACT:It is an important and difficult work to measure the ESDD on a suspension porcelain insulator surface on-site. This paper described the on-site ESDD measuring method in which the contamination of an insulator surface was wetted and the conductance measured. Two types of sensor were designed. Parameters of the measuring power system and the contamination wetting way were selected. This method was compared with the traditional brushing one which is the mainly method so far. The test results on the insulator surface have demonstrated that the method to measure the ESDD on-site is feasible.

KEY WORDS:ESDD; conductance ; sensor; on-site2 引言长期以来,瓷质绝缘子污闪事故屡屡发生,造成巨大经济损失。因此对污秽度进行测量,以便确定是否清扫是十分重要的。52年代日本首先使用等值盐密来作为污秽程度的特征量,62年代初我国东北电网也进行等值盐密的测量。2977年在全国电力系统广泛开展此项测量工作,在随后制订的污秽等级标准中将其作为划分污秽等级的一个重要依据[2]。现在等值盐密已成为世界范围内广泛采用的一个污秽参数。但目前的测量方法,操作繁琐,容易产生误差,不适合现代电力系统发展的需要。于是研究如何对等值盐密进行现场测量,使其更可靠、简单、经济、方便具有现实意义。2 现场测量的基本原理2.2 基本原理盐分溶解水中,使水溶液具有了导电性,通过测量此溶液的电导可计算出含盐量,从而求出等值盐密。现场测量就是通过一特制的采样探头和配套的测量系统,该探头能自带充足水分,润湿绝缘子表面,使附着于绝缘子表面的盐分溶解,通过测量其电导,处理后给出等值盐密值。测量原理如图2。图2 测量湿润污层电导

Fig.2 The measurement of conductance

on wetted insulator surface式中 Rt为测量样品等效电阻;Vs为信号源;R为串联电阻;γ为测量样品的电导值。2.2 测量处理系统根据上述基本原理,设计出测量仪处理系统。首先在实验室精确测量电导与等值盐密的关系,制成一个电子表格,储存在EPROM 27C228内。现场测量时,电路根据测量的电导信号自动查表,把查到的等值盐密送给语音处理芯片由喇叭播出。整个系统主要由单片机控制。由于此方法采用查表的方法,只要在实验室准确测量出盐密与电导的数据对应关系,现场测量时保持测量条件一致,就可以准确测量实际绝缘子的盐密值。而不一定非得找出在此类测量系统中盐密与电导的关系解析式。3 测量方法测量方法主要由测量探头决定,后续处理系统基本一样。